Make-up air for eleven kitchens under one roof

Cawdrey Gate Food Hall

Stainless extract canopies over a commercial kitchen line

A food hall replaces one kitchen extract with eleven, and the air those canopies pull out has to be put back. Untempered make-up air in July arrives at outside condition, and outside condition in a Sheffield summer carries about ten and a half grams of water in every kilogram of air.

The unit that answers that is the coil drawn on our home page. It is a six-row chilled-water coil on a 2,000 l/s make-up air unit, and it is doing two separate jobs at once: dropping the air from 28 °C to 12.7 °C, and taking 2.2 grams per kilogram of water out of it on the way. The second job is three-quarters of the drain load and a quarter of the duty.

What we changed on site was the drain. The unit had been specified before we were appointed and the drain was 22 mm, run level, into an unvented trap. Nineteen litres an hour has to go somewhere.

The coil on this job

Coil 01 — condensing

MUA-1, Cawdrey Gate

Make-up air, 100% outside air, six-row chilled-water coil at 6/12 °C.

air on air off 6 rows · 2,000 l/s 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 dry bulb °C g/kg saturation coil surface 11 °C dew point 15 °C on
Coil schedule for MUA-1, Cawdrey Gate
  dry bulb humidity ratio RH enthalpy
Air on 28 °C 10.6 g/kg 45% 55.2 kJ/kg
Air off 12.7 °C 8.39 g/kg 92% 34 kJ/kg
Duty 51 kW total 37.7 kW sensible 13.37 kW latent SHR 0.74
Condensate 19.1 litres per hour to drain